The core and coil assembly is wound and encapsulated in a molded cast resin with various window sizes from 6” up to 44”.
The coil is specially designed and arranged for 3-phase conductor use to prevent localized saturation and/or nuisance tripping. The secondary terminals have ¼”-20 studs with associated hardware located inside a removable terminal box with two (2) 1” NPT conduit hubs.
The PSZ-981 indoor/outdoor zero-sequence current transformer is a 600 volt, 10kV BIL rated unit and is designed to fi t over a variety of specifi ed primary conductor sizes. The insulation of the three phase primary conductors provide the dielectric protection for the zero-sequence CT. Primary current ratios are available from 50:5 to 200:5 at 60 Hertz (Hz) with a Rating Factor of up to 3.0. This dry-type, solid-cast, zero-sequence CT will operate with relay accuracy for ground fault detection applications.
Mfr. Part No. | Description |
PSZ–981 | Indoor/Outdoor 600V, 10kV BIL, Single Ratios |